CO2 Mk9 Detector Set 4A

N.º de artículo 2049
The MK9 sensor is a precision instrument that continuously monitors temperature and CO2 gas concentration using infrared analysis. It has red, yellow and green LED lights and an intermittent buzzer for low alarm and continuous sound for high alarm. The MK9 performs a self-calibration at regular
Este producto no puede ser pedido en este momento.
Descripción
The MK9 sensor is a precision instrument that
continuously monitors temperature and CO2 gas
concentration using infrared analysis. It has red,
yellow and green LED lights and an intermittent
buzzer for low alarm and continuous sound for
high alarm. The MK9 performs a self-calibration at
regular intervals, eliminating the need for service
calibration.

>Most cost effective CO2 safety system currently available
> Four alarm levels fulfill all U.S. CO2 safety codes and norms
> Central unit makes non-smelling invisible CO2 gas visible and
advises what to do in different alarm situations
> Automatic calibration is safer and requires zero maintenance
> System is expandable, up to eight sensors
> System can be connected to an existing fire alarm system
that is connected to the fire department

Includes:
MK9 CO2 Central Unit
MK9 CO2 Sensor
Horn/Strobe LED with 3 ft (0.9144m) Cable
1 Red 15 ft (4.572m) Cable
1 Red 30 ft (9.144m) Cable
1 Blue 15 ft (4.572m) Cable
RJ45 1-1 Splitter
RJ45 1-2 Splitter
Transformer 1A & Plug - UL
Plug-Lock
Bag with 6 Screws and Plug
Sign CO2 Safety System
Sign Horn/Strobe
Installation Manual
Quick-Guide

SPECIFICATIONS:
MK9 CENTRAL UNIT
Operating Temp: 32° to 102° F (0° to 40°C)
Operating Humidity: 0-90% RH
Power Supply: 24V DC
Power Usage: No Alarm Status: 21 mA
Alarm Status: 32 mA
Acoustic Signal Strength: 80 dBa (1m)
Size (LxWxD): 3.52” x 6.32” x 1.47”
(89.6mm x 160.5mm x 37.4mm)

MK9 SENSOR
Operating Temp: 32° to 102° F (0° to 40°C)
Operating Humidity: 0-95% RH (non condensing)
Power Supply: 24V DC
Power Usage: No Alarm Status: 56 mA
Alarm Status: 68 mA
Acoustic Signal Strength: 76 dBa (1m)
Automatic Calibration: 60 Days
Size (LxWxD): 3.52” x 6.32” x 1.47”
(89.6mm x 160.5mm x 37.4mm)

HORN/STROBE
Operating Temp: 23° to 122°F (-5° to 50°C)
Power Supply: 18-24V DC
Power Usage: 120 mA @ 24V DC supply
Acoustic Signal Strength: 110 dB / 1 m
Flash Intensity: 115 CD
Flash Frequency: 65/min
Size (LxWxD): 5.3” x 4.5” x 2.4”
(134mm x 115mm x 61mm)